Radiant Heat Reducing Glazing Solution

Straight From the Source
See the SuperLite I-XL Informational Bulletin

SuperLite I-XL is a patented breakthrough, monolithic technology that reduces the transfer of radiant heat by reflecting heat back towards the fire source. It minimizes the threat of scorching heat which can limit the safe egress of occupants and can cause the fire to spread to adjacent areas. SuperLite I-XL 45/60, the first and only product of its kind to be introduced in the USA, was developed by SAFTI FIRST in 1993 and has been installed in locations throughout the USA Authorities having jurisdiction (AHJs) across the country have approved this non-hose stream tested product because of its ability to reflect radiant heat and stay in the opening for over one hour, allowing for safe egress of occupants. Most AHJs recognize that the hose stream test was designed for structural building integrity and not as a thermal stress test for fire-rated glazing. Sprinkler activation does not compromise the performance of SuperLite I-XL.

For over 20 years, Europe, Japan and other countries have taken advantage of the enhanced safety performance of products like SuperLite I-XL. This radiant heat reducing fire glazing is an excellent choice for schools, hospitals, historical renovations, wilderness/urban interface areas, property line applications, or any areas where safe egress, impact safety and protection from the dangers of radiant heat are a concern. SuperLite I-XL provides greater radiant heat and impact protection than any other monolithic glazing, including ceramics, and is a low cost replacement for unsafe traditional wired glass. It is available in non-directional insulated or directional monolithic makeups. Fire fighters along with code officials have stated their favor of a product like SuperLite I-XL because it is quick and safe to remove in the event of a fire, allowing for access, smoke release and safe egress of occupants.

FEATURES 
  • Patented specialty tempered glazing tested without hose stream that provides partial radiant heat protection not available with ceramics.
  • Accepted by the GSA and AHJ’s across the country as an economical and value added alternative to traditional unsafe wired glass and expensive ceramics.
  • Meets the highest human impact safety requirements.
  • Approved for 20 minute applications without limitations.
  • Received a General Approval from the City and County of Los Angeles (RR25655).
  • Regularly specified for use in urban-wildfire exterior applications and perfect for property line requirements.
  • Available in specialty architectural make-ups.
  • Lifetime warranty.
  • USA manufactured for fast delivery and competitive pricing.

For information on obtaining AHJ Approval for SuperLite I-XL,
click here.

Fire Rating Application Max CV Area Max CV W Max CV H Stops

20 minutes

Steel Doors

3,341sq. in.

35-1/8”

95-1/8”

5/8”

20 minutes

Steel Sidelites,
Windows and
Transoms

5,760 sq. in.

96”

96”

5/8”

45 minutes Steel Doors 3,341 sq. in. 35-1/8” 95-1/8” 5/8”
45 minutes Steel Sidelites, Windows and Transoms 5,760 sq. in. 96” 96” 5/8”

60 minutes

Steel Doors (NT)

3,341 sq. in.

35-1/8”

95-1/8”

5/8”

60 minutes

Steel Sidelites,
Windows and
Transoms (NT)

3,388 sq. in.

44”

95-1/8”

5/8”

 
SPECIFICATIONS 

Thickness: 1/4” (6 mm)

Weight: 3.0 lbs./sq.ft.

Sound Transmission Rating: STC 28

Fire Rating: 20-60 minutes without hose stream.

Impact Safety Rating: CPSC 16 CFR 1201 Cat. I and II

Solar Heat Gain Coefficient: 0.70 SHGC

LISTINGS and WARRANTY 
SuperLite I-XL is listed and labeled by Intertek/Warnock-Hersey Inc. and Underwriters Laboratories, nationally recognized testing laboratories approved by OSHA.

   

Requires AHJ approval for 45-60 minute applictions because this is a directional product that is tested without hose stream. Please visit www.safti.com/AHJ for more information. For non-directional make-up, see SuperLite I-XL IGU

See Warranty

 

STANDARDS 

UL 9, UL 10B, UL 10C, NFPA 80,
NFPA 252, NFPA 257, ASTM E152,
ASTM E163, ASTM E2074, ASTM E2010-01, CPSC 16 CFR 1201 Cat. II

U.S. Pat. No. 5,910,620

This product requires AHJ approval because it does not pass the
hose stream portion of the fire test.